Fluke 1587 FC Insulation Multimeter

Fluke 1587 FC Insulation Multimeter is rated 4.7 out of 5 by 31.
  • y_2024, m_11, d_16, h_7
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.42
  • cp_2, bvpage2n
  • co_hasreviews, tv_5, tr_26
  • loc_en_US, sid_3739310948404, prod, sort_[SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_fluke
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getAggregateRating, 211.64ms
  • REVIEWS, PRODUCT
  • Fluke 1587 FC Insulation Multimeter
  • Fluke 1587 FC Insulation Multimeter
  • Fluke 1587 FC Insulation Multimeter
  • Fluke 1587 FC Insulation Multimeter

Key features

  • Safety first. Connect the insulation tester then keep yourself out of harm's way by monitoring your test measurements remotely.
  • Prove your job is done right by quickly seeing and sharing insulation resistance test results wirelessly with your smartphone.
  • Quickly find problems by saving and comparing measurements over time on a wireless device.

Product overview: Fluke 1587 FC Insulation Multimeter

Keep yourself safe. Find hidden problems faster. Put the paperwork down.

Fluke Connect + Fluke's 1587 FC Insulation Multimeter helps you identify tough problems, fix, and wirelessly communicate your work quickly and easily - all at a safe distance.

Add diagnostics with Fluke Connect

The Fluke 1587 FC is Fluke Connect-enabled so you can download the free Fluke Connect® Measurements app to your smartphone and gain additional functions, including:

  • Safety first. Keep yourself out of harm’s way by monitoring your test measurements remotely.
  • Prove your job is done right by quickly seeing and sharing measurement results wirelessly with your smartphone.
  • Quickly find problems by saving and comparing measurements over time on a wireless device.
  • PI/DAR timed ratio tests with TrendIt™ graphs to identify moisture and contaminated insulation problems faster
  • Memory storage through Fluke Connect that saves measurements to your phone or the cloud and eliminates the need to write down results. Reduces errors and saves data for historical tracking over time
  • Temperature compensation to establish accurate baselines and relevant historical comparisons
  • Historical tracking and trending of assets to identify insulation degradation over time and allow real-time decisions to be made in the field with Fluke Connect® Assets (sold separately)
  • Provides memory storage through Fluke Connect Measurements to eliminate the need to write down results
  • Includes live circuit detection to prevent insulation test if voltage >30 V is detected
  • Supports historical tracking and asset trending of assets to identify degradation over time with Fluke Connect® Assets (sold separately)
  • Incorporates VFD low-pass filter for accurate variable frequency motor drive measurements
  • Includes auto-discharge of capacitive voltage for added user protection
  • Measures ac/dc voltage, dc millivolts, ac/dc milliamps, resistance, and continuity
  • Includes capacitance, diode test, temperature, min/max, frequency measurements and insulation test smoothing reading
  • Automatically powers off to save battery power
  • Comes with remote probe, test leads, alligator clips, K-type thermocouple, hard case, and three-year warranty.

Useful resources and rugged tools for Solar professionals

 
 Fluke 115 Field Technicians Digital MultimeterFluke 87V Industrial MultimeterFluke 3000 FC Series Wireless MultimeterFluke 1587 FC Insulation MultimeterFluke 279 FC True-rms Thermal Multimeter
CAT ratingCAT III 600 VCAT III 1000 V
CAT IV 600 V
CAT III 1000 V
CAT IV 600 V
CAT III 1000 V
CAT IV 600 V
CAT III 1000 V
CAT IV 600 V
True-rms readings
Voltage AC/DC600 V1000 V1000 V1000 V1000 V
Current AC/DC10 A10 A400 mA400 mA2500 A AC (with iFlex)
Resistance40 MΩ50 MΩ50 MΩ50 MΩ50 MΩ
Capacitance10,000 μF10,000 μF10,000 μF10,000 μF10,000 μF
Temperature--200.0 °C to 1090 °Cwith t3000 FC-40 °C to 537 °CInfrared camera
-10 °C to 200 °C
Infrared camera----
Additional
measurement
capabilities
Continuity/diode testFrequency,
continuity/diode test,
motor drive (VFD)
measurement,
duty cycle,
microamps, analog
bar graph, relative
reference
Frequency,
continuity/diode test.
Able to connect to
three 3000 FC
modules.
Frequency, Pi/DAR
timed ratio tests,
continuity/diode test, motor drive (VFD)
measurement,
microamps, relative
reference
Frequency,
continuity/diode test,
motor drive (VFD)
measurement

What's in the box:

  • Fluke 1587 FC Insulation Multimeter
  • Remote probe
  • Test leads
  • Alligator clips
  • K-type thermocouple
  • Soft case
  • User documentation

Specifications: Fluke 1587 FC Insulation Multimeter

Electrical Specifications
AC voltage measurement
Range
600.0 mVResolution0.1 mV
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)
6.000 VResolution0.001 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)
60.00 VResolution0.01 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)
600.0 VResolution0.1 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)¹
1000 VResolution1 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(2% + 3)
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts)±(2% + 3)¹
¹ 1 kHz bandwidth
Low-Pass Filter Voltage 
Range
600.0 mVResolution0.1 mV
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)+(2% + 3), -(6% - 3)
6.000 VResolution0.001 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)+(2% + 3), -(6% - 3)
60.00 VResolution0.01 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)+(2% + 3), -(6% - 3)
600.0 VResolution0.1 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(1% + 3)
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)+(2% + 3), -(6% - 3)
1000 VResolution1 V
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts)±(2% + 3)
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts)+(2% + 3), -(6% - 3)
DC Voltage Measurement
RangeResolutionAccuracy ±(% of Rdg + Counts)
6.000 V dc0.001 V±(0.09% + 2)
60.00 V dc0.01 V±(0.09% + 2)
600.0 V dc0.1 V±(0.09% + 2)
1000 V dc1 V±(0.09% + 2)
Input impedance 10 MΩ (nominal), <100 pF
Normal mode rejection ratio >60 dB @ 50 Hz or 60 Hz
Common mode rejection ratio >120 dB @ dc, 50 Hz or 60 Hz (1 k unbalance)
Accuracies apply to ± 100% of range
DC Millivolts Measurement
RangeResolutionAccuracy ±(% of Rdg + Counts)
600.0 mVdc0.1 mV±(0.1% + 1)
DC and AC Current Measurement
AC 45 Hz to 1000 Hz
Range400 mA
Resolution0.1 mA
Accuracy ±(% of Rdg+Counts)±(1.5% + 2)¹
Burden voltage (Typical)2 mV/mA
Range60 mA 
Resolution0.01 mA 
Accuracy ±(% of Rdg+Counts)±(1.5% + 2)¹
Burden voltage (Typical)2 mV/mA
DC
Range400 mA
Resolution0.1 mA
Accuracy ±(% of Rdg+Counts)±(0.2% + 2)
Burden voltage (Typical)2 mV/mA
Range60 mA
Resolution0.01 mA
Accuracy ±(% of Rdg+Counts)±(0.2% + 2)
Burden voltage (Typical)2 mV/mA
Overload600 mA for 2 minutes maximum
Fuse protection for mA input0.44 mA, 1000 V, IR 10 kA
AC conversionInputs are ac-coupled and calibrated to the rms value of sine wave input
Conversions are true-rms responding and specified from 5% to 100% of range. Input signal crest factor can be up to 3 up to 300 mA, decreasing linearly to crest factor ≤1.5 at 600 mA. For non-sinusoidal waveforms add +(2% reading + 2% FS) typical, for a crest factor up to 3.
¹ 1 kHz bandwidth
Ohms Measurement
RangeResolutionAccuracy +(% of Rdg+Counts)¹
600.0 Ω0.1 Ω±(0.9% + 2)
6.000 kΩ0.001 kΩ±(0.9% + 2)
60.00 kΩ0.01 kΩ±(0.9% + 2)
600.0 kΩ0.1 KΩ±(0.9% + 2)
6.000 MΩ0.001 MΩ±(0.9% + 2)
50.0 MΩ ²0.01 MΩ±(1.5% + 3)
Overload protection 1000 V rms or dc
Open circuit test voltage <8.0 V dc
Short circuit current <1.1 mA
¹ Accuracies apply from 0% to 100% of range
² Up to 80% relative humidity
Diode Test
Diode test indicationDisplay voltage drop: 0.6 V at1.0 mA nominal test current:
Accuracy±(2% + 3)
Continuity Test
Continuity indicationContinuous audible tone for testresistance below 25 Ω and off above 100 Ω. Maximum Reading; 1000 Ω
Open circuit voltage<8.0 V
Short circuit current1.0 mA typical
Overload protection1000 V rms
Response time>1 m sec
Frequency Measurement
RangeResolutionAccuracy ±(% of Rdg+Counts)
99.99 Hz 0.01 Hz ±(0.1% + 1)
999.9 Hz 0.1 Hz ±(0.1% + 1)
9.999 kHz 0.001 kHz ±(0.1% + 1)
99.99 kHz 0.01 kHz ±(0.1% + 1)
Frequency Counter Sensitivity
600.0 mV ac V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz 100.0 mV 
V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz150.0 mV 
DC Trigger Levels¹ to 20 kHz²NA
6.0 V V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz 1.0 V 
V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz1.5 V 
DC Trigger Levels¹ to 20 kHz²-400.0 mV and 2.5 V
60.0 V V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz 10.0 V 
V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz36.0 V 
DC Trigger Levels¹ to 20 kHz²1.2 V and 4.0 V
600.0 V V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz 100.0 V 
V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz-
DC Trigger Levels¹ to 20 kHz²12.0 V and 40.0 V
1000.0 V V ac Sensitivity (RMS Sine Wave)¹  5 Hz to 20 kHz 300.0 V 
V ac Sensitivity (RMS Sine Wave)¹  20 kHz to 100 kHz-
DC Trigger Levels¹ to 20 kHz²12.0 V and 40.0 V
¹ Maximum input for specified accuracy = 10x range (1000 V max). Noise at low frequencies and amplitudes may affect accuracy
² Usable to 100 kHz with full scale input
Capacitance
Range Resolution Accuracy ±(% of Rdg+Counts)
1000 nF 1 nF±(1.2% + 2)
10.00 μF 0.01 μF±(1.2% + 2)
100.0 μF 0.1 μF±(1.2% ±90 counts)
9999 μF 1 μF±(1.2% ±90 counts)
Temperature Measurement
Range Resolution Accuracy ±(% of Rdg+Counts)¹
-40 ° C to 537 ° C 0.1 °C ±(1% + 10 counts)
-40 ° F to 998 ° F 0.1 °F ±(1% + 18 counts)
¹ Accuracies apply following 90 minutes settling time after a change in the ambient temperature of the instrument
Insulation Specifications
Measurement range0.01 MΩ to 2 GΩ
Test voltages50, 100, 250, 500, 1000 V
Test voltage accuracy+20%, -0%
Short-circuit test current1 mA nominal
Auto dischargeDischarge time <0.5 second for C = 1 μF or less
Live circuit detectionInhibit test if terminal voltage > 30 V prior to initialization of test
Maximum capacitive loadOperable with up to 1 μF load
Output Voltage
50 V (0% to +20%)Display range0.01 to 6.00 MΩ
Resolution0.01 MΩ
Test current1 mA @ 50 kΩ
Resistance accuracy ±(% of Rdg + Counts)±(3% + 5 counts)
Display range6.0 to 50.0 MΩ
Resolution0.1 MΩ
Test current1 mA @ 50 kΩ
Resistance accuracy ±(% of Rdg + Counts)±(3% + 5 counts)
100 V (0% to +20%)Display range0.01 to 6.00 MΩ
Resolution0.01 MΩ
Test current1 mA @ 100 kΩ
Resistance accuracy ±(% of Rdg + Counts)±(3% + 5 counts)
Display range6.0 to 60.0 MΩ
Resolution0.1 MΩ
Test current1 mA @ 100 kΩ
Resistance accuracy ±(% of Rdg + Counts)±(3% + 5 counts)
Display range60 to 100 MΩ 
Resolution1 MΩ
Test current1 mA @ 100 kΩ
Resistance accuracy ±(% of Rdg + Counts)±(3% + 5 counts)
250 V (0% to +20%)Display range0.1 to 60.0 MΩ 
Resolution0.1 MΩ
Test current1 mA @ 250 kΩ 
Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
Display range60 to 250 MΩ 
Resolution1 MΩ
Test current1 mA @ 250 kΩ 
Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
500 V (0% to +20%)Display range0.1 to 60.0 MΩ
Resolution0.1 MΩ
Test current1 mA @ 500 kΩ 
Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
Display range60 to 500 MΩ
Resolution1 MΩ
Test current1 mA @ 500 kΩ 
Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
1000 V (0% to +20%)Display range0.1 to 60.0 MΩ 
Resolution0.1 MΩ
Test current1 mA @ 1 MΩ
Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
Display range60 to 600 MΩ 
Resolution1 MΩ
Test current1 mA @ 1 MΩ
Resistance accuracy ±(% of Rdg + Counts)±(1.5% + 5 counts)
Display range0.6 to 2.0 GΩ 
Resolution100 MΩ 
Test current1 mA @ 1 MΩ
Resistance accuracy ±(% of Rdg + Counts)±(10% + 3 counts)
General Specifications
Maximum voltage applied to any terminal and common1000 V
Storage temperature-40 °C to 60 °C (-40 °F to 140 °F)
Operating temperature-20 °C to 55 °C (-4 °F to 131 °F)
Temperature coefficient0.05 x (specified accuracy) per °C for temperatures <18 °C or >28 °C (<64 °F or >82 °F)
Relative humidityNoncondensing
0% to 95% @ 10 °C to 30 °C (50 °F to 86 °F)
0% to 75% @ 30 °C to 40 °C (86 °F to 104 °F)
0% to 40% @ 40 °C to 55 °C (104 °F to 131 °F)
VibrationRandom, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument
Radio frequency communication2.4 GHz ISM Band
Radio frequency certificationFCC: T68-FBLE, IC: 6627A-FBLE
Electromagnetic Compatibility 
InternationalIEC 61326-1:Portable Electromagnetic Environment; IEC 61326-2-2 CISPR 11: Group 1, Class A
Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself.
Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes.  There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances.
Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object. The equipment may not meet the immunity requirements of this standard when test leads and/or test probes are connected.
Korea (KCC)Class A Equipment (Industrial Broadcasting & Communication Equipment)
Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes.
USA (FCC)47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
Enclosure protectionIEC 60529: IP40 (non-operating)
Safety
IEC 61010-1Pollution Degree 2
IEC 61010-2-033CAT IV 600 V / CAT III 1000 V
Batteries Four AA batteries (IEC LR6)
Battery lifeMeter use 1000 hours; Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
Size (H x W x L)5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in)
Weight550 g (1.2 lb)
AltitudeOperating2000 m
Storage12,000 m
Over-range capability110% of range except for capacitance which is 100%
Frequency overload protection<107 V Hz
Fuse protection for mA input0.44A, 1000 V, IR 10 kA

Models: Fluke 1587 FC Insulation Multimeter

FLK-1587-FC
Fluke 1587 FC Insulation Multimeter

Buy it
Includes:
  • Remote probe
  • Test leads
  • Alligator clips
  • K-type thermocouple
  • Soft case
  • User documentation
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getContent, 120ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: HTTP status code of 404 was returned;
Rated 5 out of 5 by from So Very Reliable I purchased the 1587 to be our shop meter. It is never easy to find as people use it and want to keep it. Coupled with the Fluke amp clamp, this meter has everything we need for our maintenance shop.
Date published: 2016-12-12
Rated 5 out of 5 by from Fluke 1587C I have purchased Fluke equipment in the past, so it was only natural to go to Fluke again when I wanted an Insulation tester. I have been extremely happy with the construction, durability, and ease of use. I would highly recommend it to anyone who is looking for a high quality tester.
Date published: 2016-12-12
Rated 5 out of 5 by from The One Tester to Have! The 1587 is the only meter I need to perform everything from measuring continuity of low voltage signals to testing insulation breakdown levels on high voltage AC and DC automotive systems.
Date published: 2016-12-11
Rated 5 out of 5 by from Great Meter with Bluetooth I replaced my 1587 meter with the 1587FC about 6 months ago and I like the Bluetooth connection feature. I can connect the meter at one location and using my cell phone read the output when I am troubleshooting up and down the line.
Date published: 2016-12-09
Rated 5 out of 5 by from Versatile Had one for a while now. A remarkably versatile easy to use meter - a real time saver with so much functionality in one meter - one of the best fluke products ever.
Date published: 2016-12-08
Rated 5 out of 5 by from Best meter I've used in .35 years of field service This is my 3rd Fluke meter purchase in 35 years of providing industrial equipment field service. Each meter better than the last. Each one excellent in accuracy, quality and speed. The 1587 allows me to give my customers fast, accurate service evaluations of their motors, vfd drives and electrical control systems. And to make this meter even better it is made in the USA. I trust only Fluke meters when it comes to providing the very best in customer service. Thanks Fluke for consistently providing the very best in electrical test equipment.
Date published: 2016-12-07
Rated 5 out of 5 by from Great tester! If you need a DMM and an insulation tester, this is a great tester. Great additional features through the iPhone.
Date published: 2016-12-07
Rated 5 out of 5 by from 1587 FC is a Fantastic diagnostic tool! I have now owned this meter for about a year and am extremely pleased with it. It has great voltage sensitivity down to the millivolt level. This meter has all the normal functions of most DMM's and adds insulation resistance measurements as well! I highly recommend this meter for all skilled electricians wanting to step up their diagnostic capabilities with one meter.
Date published: 2016-12-07
Rated 5 out of 5 by from Solid insulation tester This was an upgrade from the first generation model 1587 and I can say it is worth every penny. Hands down, the best feature is the Bluetooth connection via Fluke Connect. I test countless motors in an industrial setting and logging the insulation results over time is essential. Logging that data on my phone is a massive time saver and ensures accuracy. Similarly, logging PI/DAR timed ratio tests with Fluke Connect is key to long term proactive analysis of motors.
Date published: 2016-12-07
Rated 5 out of 5 by from 1587FC - time and money saver! I recently purchased this unit after seeing my lead electrician save time diagnosing motors with an older unit. I am his backup and this unit was quick and easy to learn to do the basics. I am by no means a complete expert, but I can quickly rule in or rule out the "bad motor" that gets thrown under the bus so many times by mechanics.
Date published: 2016-12-07
Rated 5 out of 5 by from Excellent Meter This is an excellent meter for the price point. It gives you the ability to test motor insulation, among many other features, temp, amps, and volts to name a few. This unit gets heavy use and hasn't failed me once
Date published: 2016-12-07
Rated 5 out of 5 by from Great Meter This meter was a great price, very portable and has all the features I was looking for!
Date published: 2016-12-07
Rated 5 out of 5 by from Very Robust We have been using 5 of these offshore over the past few years. They have held up great to offshore abuse. We calibrate them annually, but they have never required any adjustments. I will continue to use the newer model (FC) as our group continues to grow.
Date published: 2016-12-07
Rated 5 out of 5 by from Great tool I bought this meter 1 year ago. I use it to test chiller motors and supply fan motors. It is a great tool for maintenance and troubleshooting. I have great confidence in this meter and the information that it tells me. This meter exceeded my expectation and will be a valued tool in my tool bag for many years to come.
Date published: 2016-12-07
Rated 5 out of 5 by from Upgraded from my 1587 I'm an industrial and commercial electrician. I originally purchased a 1587 as part of the 1587-MDT (Motor Drive Troubleshooting) Kit, with the 400A current clamp, thermocouple, and 9040 Phase Rotation Indicator. I often troubleshoot and commission motors, and the 1587 was my go-to DMM. It's now been replaced by the 1587FC The added features of Fluke Connect, the automated temperature correction when conducting IRT (Insulation Reisitance Tests), and automated PI (Polarization Index) and DAR (Dialectric Absorbtion Ratio) tests have simplified and streamlined my troubleshooting procedure. Documentation of troubleshooting and of pre-start motor commissioning or re-commissioning now is clear, and simple. The graph of an IRT for a borderline motor winding really helps me explain to a customer the problem, or potential problem, with a motor. And, it's saved customers money when I can document a motor's or compressor's health where other technicians have played the "it's a bad motor" card. The most innovative use I found for my 1587FC is in tuning a 0-10VDC PID (Poportional gain, Integral gain, Derivitive gain) pressure control loop. The realtime graphing function with Fluke Connect allowed me to see the resultant pressure of the VFD's response in realtime as I adjusted the P, I, and D values of the VFD. And the value of documentation is priceless.
Date published: 2016-10-29
Rated 5 out of 5 by from One of hte Best Multi Meters Yet I've been using this Meter for almost 2yrs now, from just checking voltage all the way to checking insulation in motors. I would recommend this meter to any Industrial Electrician.
Date published: 2012-10-19
Rated 5 out of 5 by from simple and easy Everything on this meter is simple and easy to use. Big and bright display. I'm an automotive technican and I use this meter for everything. Fluke meters by far in my opinion are the best.
Date published: 2012-06-07
Rated 5 out of 5 by from tool mgr i have a fluke 16 multimeter and have been using for over 11 years now, i think they are the best on the market. this one has never failed and that in itself is a selling point to me.as far as i'm concerned fluke brands are all i buy. thank you for a great product.
Date published: 2012-06-07
  • y_2024, m_11, d_16, h_7
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.42
  • cp_2, bvpage2n
  • co_hasreviews, tv_5, tr_26
  • loc_en_US, sid_3739310948404, prod, sort_[SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_fluke
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getReviews, 49.13ms
  • REVIEWS, PRODUCT
Please enable cookies to view product reviews.