Measuring motor shaft voltage discharges with Fluke MDA-550 Motor Drive Analyzer

 

Shaft voltage discharges

Capacitive coupling between a motor’s stator and rotor can create a voltage on a motor shaft. For this reason, bearings in electric motors can suffer from wear and tear caused not only by the rotation of the shaft but also by electric currents flowing from the motor shaft to ground through the bearings. Motors powered by sine wave ac power may have shaft/bearing-to- frame voltages of about 1 to 2 V. Motors powered by the rapidly switching waveforms of variable frequency drives (VFD) may, however, have shaft/bearing-to-frame voltages as high as 8 to 15 V. Voltages at these levels can overcome the insulating properties of bearing grease and the resulting sparks can cause pitting, fluting, fusion craters, and, eventually, premature failure of the bearings and motor.

Fluting Bearing Race
Fluting of a bearing race caused by bearing currents (Photo courtesy of Electro Static Technology).
Using MDA
Measuring motor shaft voltage with the shaft voltage probe kit

Shaft voltage probe

Shaft voltage is only present while the motor is energized, rotating, and warmed up to normal operating temperature. Measuring the voltage of a rap- idly spinning motor shaft can  be difficult and dangerous. A shaft voltage probe uses a small conductive brush to safely and conveniently make electrical connections to motor shafts. The reference contact of the probe is connected to ground at the motor housing. The measurement can be done on both the drive and non-drive ends of the motor.

Measuring device

The MDA-550 is designed to quickly and easily test and troubleshoot typical problems on three-phase and single-phase inverter type motor drive systems. Next to the 4-channel portable oscilloscope and recorder functionality, specific motor drive analysis functions offer step-by-step setup guidance with on-screen information. This makes it easy to configure the analyzer and get the drive measurements from the power input to the installed motor, including shaft voltage measurements.

Shaft-voltage spikes can be exceedingly fast, even below the microsecond measurement range. The Fluke MDA-550’s high 500 MHz bandwidth and fast sampling rate (up to 5 Gsample/s) make it ideal for measuring rapid changes in voltages.

F-MDA-550-01a
Fluke MDA-550 Motor Drive Analyzer

Measurement results

The default motor shaft voltage measurement shows voltage waveforms as measured on the motor shaft itself. The voltage peak-peak value displayed at the top of the screen identifies the maximum level of the captured waveform, which is already an indication that high voltage levels are present on the shaft. However, the frequency with which these fast discharges occur cannot be determined this way. Utilizing the “EVENTS ON” function, the MDA-550 will display waveforms with discharges based on a pre-defined minimum voltage difference and maximum time difference.

The display is updated with each waveform captured that has a steeper rise- or fall-time, along with the number of detected events per second. Discharge waveforms will show an increase in voltage to ground followed by a sharp vertical line to ground at the moment of discharge. For a detailed analysis of the last captured waveform, the MDA-550 offers the "REPLAY" feature with a buffer of the screens for the last 100 waveforms captured. The screen can be individually selected or displayed as an animation.

Voltage discharges of greater than 15 V and transition times faster than 50 nanoseconds can point to discharges capable of damaging bearings. However, this alone is not enough to determine potential damage to a bearing as there are many other factors influencing this.

If excessive shaft voltages are detected, it is a good practice to see if voltage discharges can be reduced by adapting the cabling, grounding, drive parameters, or lubricant. If this is not possible or does not help mitigate the problem, shaft grounding devices or an isolated shaft are useful alternatives. The effects of these shaft voltage mitigation efforts can easily be understood by comparing the number of events recorded before and after changes were implemented.

Use the Motor Shaft Voltage function in the Fluke Motor Drive Analyzer and avoid costly motor repairs and unexpected production downtime

Motor Shaft Events Off
Motor shaft voltage signal with events turned off shows all captured signals with peak-peak voltage reading
Motor Shaft2
Shaft voltage discharge events with specified minimum voltage and maximum fall- or risetime in tale form
Motor Shaft Event Wave
With Events on, only waveforms with a specified minimum voltage and maximum fall- or risetime are displayed
Motor Shaft Replay
The replay function shows the last 100 captured waveforms for advanced analysis


Do you want to learn more?

Fill out our short Demo Request form and we will contact you to schedule your personal demo from a qualified Fluke engineer. You'll get a hands-on demonstration of the instrument in your workplace, focused on the measurements you need. You'll see how easy our instruments are to use, and receive training and advice on both the instrument and related accessories. So, if you buy, you're sure to select the instrument that's right for you, and get the most out of it!


 

You might also be interested in

Chat with ourFluke assistant
Clear Chat