Fluke 1750 Three-Phase Power Quality Logger

Model#:Fluke 1750Part#:4756213UPC#:0 95969 81522 2
Fluke 1750 Three-Phase Power Quality Logger is rated 4.5 out of 5 by 2.
  • y_2024, m_11, d_18, h_5
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.42
  • cp_1, bvpage1
  • co_hasreviews, tv_0, tr_2
  • loc_en_US, sid_1627906637876, prod, sort_[SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_fluke
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getAggregateRating, 26.27ms
  • REVIEWS, PRODUCT
  • Fluke 1750 Three-Phase Power Quality Recorder
Discontinued

Key features

  • Three-phase power quality recorder with an Android tablet wireless front panel interface
  • Complies with IEC 61000-4-30 Class-A standards for correct evaluation of all measured values
  • Supports quick and reliable configuration even in awkward test locations with the wireless interface that provides a window into what the instrument is recording
This product is discontinued or reclassified

Product overview: Fluke 1750 Three-Phase Power Quality Logger

Record every power quality paramater, every cycle, all the time

Setting up a power quality analyzer to capture detailed power quality data has never been easier that it is with the Fluke 1750. The only things you need to know are the system voltage, frequency and the power configuration (delta or wye). The analyzer then captures the most important data for up to 30 days without losing the most important details. These power meters automatically record every power quality parameter and event, on every cycle – all the time. Once the data is captured download via Ethernet or directly to 2GB SD card (without the need of any other device). The Fluke 1750 features a wireless front panel for viewing measurements, data and setting up, implemented via a tablet computer using Bluetooth communication.

Common Applications

  • Long-term analysis: Uncover hard-to-find or intermittent issues; monitor critical equipment, capturing power quality events to correlate with equipment malfunction
  • Power quality surveys: Quantify power quality throughout a facility, documenting results with professional reports
  • Quality of service compliance: Validate incoming power quality at the service entrance
  • Equipment Installation/Commissioning: Benchmark: power system prior to install to insure quality of service
    • Long-Term Analysis – Uncover hard-to-find or intermittent issues.
    • Load Studies – Verify the available electrical system capacity before adding loads.

Other useful features:

  • Allows you to apply thresholds after data is collected, with Fluke Power Analyze Software–no need to worry about missed information due to incorrect setups
  • Captures every measurement, on every channel, every time with cross-channel, and current triggering capture
  • Allows you to easily analyze data and generate reports in intuitive PC software with automated EN50160 reporting and compliance
  • Automatically creates standard or customized reports with Auto Report and exports reports to almost any format including RTF (Rich Text Format) for editing in Microsoft Word.
  • Sets up in minutes with self-identifying current probes and single-lead voltage connections
  • Allows you to swap channels internally with the wireless tablet or PC when connections are not correct. No need to reconnect wires
  • Measures every parameter voltage and current on three phases, neutral, and ground
  • Offers 5 MHz, 8000 Vpk waveform capture to provide a detailed picture of even the shortest events
  • Quickly retrieves data with included SD memory card or via the 100BaseT high-speed Ethernet connection.

Specifications: Fluke 1750 Three-Phase Power Quality Logger

Technical Specifications
Power quality measurement standardsConformanceIEC 61999-1-4 Class 1, IEC 61000-4-30 Class A, S or B depending on measurement function, IEEE519, IEEE1159, IEEE1459 and EN50160
Clock/calendarLeap years, 24-hour clock
Real-time clock accuracyNot more than ±1 s/day
Internal memory capacity for dataAt least 2 GB
Maximum recording periodAt least 31 days
Measurement time controlAutomatic
Maximum number of eventsLimited only by the size of the internal memory
Power requirements100 to 240 V rms ±10%, 47-63 Hz, 40 W
Operating time during interruptions (internal UPS operation)5 minutes per interruption, 60 minutes total operating time without recharging
Dimensions215 x 310 x 35 mm (8.5 x 12.2 x 3.5 in)
Mass (weight)6.3 kg (14 lb)
InputMeasurement typesOne Phase Plus Neutral, One Phase IT No Neutral, One Phase Split Phase, Three Phase Wye, Three Phase Delta, Three Phase IT, Three Phase High Leg, Three Phase Open Leg, 2 Element Delta, 21/2 Element Wye
Input channelsVoltage: 4 channels, AC/DC
Current: 5 channels
Voltage channelsInput resistance: 2 MΩ
Input capacitance: < 20 pF
Current input characteristics2 V rms = full scale, 1 MΩ Input Impedance for ferro CTs, low impedance for Flexi-CTs
Measuring methodSimultaneous digital sampling of voltage and current. Digital PLL synchronized sampling, internal frequency reference used during voltage drops.
Synchronization and samplingPLL-synchronization sourceThe PLL synchronizes to the A-N voltage for wye power types, and to the A-B voltage for delta power types. All listed power types can be characterized as either wye or delta.
PLL lock range42.5 to 69 Hz
Sampling frequencyVoltage and current: 256 samples/cycle Inter-harmonics per IEC 61000-4-7: 2 560 points/10 cycles (50 Hz), 3072 points/12 cycles (60 Hz) Transient Voltage: 5 MHz
A/D resolutionVoltage and current: 24 bits
Transient voltage: 14 bits
Voltage and current measurementsVoltage measurement rangeAC voltage: 1000 V rms ±10% over range
DC voltage: ±1000 V + 10% over range
Voltage crest factor3 or less
Current measurement rangeDepends on current probe used
Current crest factor4 or less
RMS voltageMeasurement typeTrue rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by IEC 61000-4-30.
Measurement uncertaintyAC: ±0.2% reading ±0.1% full scale, above 50 V rms
DC: ±0.5% reading ±0.2% full scale, above 50 V dc
RMS currentMeasurement typeTrue RMS calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards
Transient voltage (impulse)Measurement typeWaveshape sampling
Full scale8000 V pk
Sample resolution200 nS
Measurement uncertainty±5% reading ±20 V (test parameters: 1000 V DC, 1000 V rms, 100 kHz)
Voltage swell (rms swell)Measurement typeTrue RMS (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines)
Displayed dataAmplitude and duration of swell
MeasurementSame as rms voltage
Voltage dip (rms sag)Measurement typeTrue RMS (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines)
Displayed dataAmplitude and duration of dip or interruption
MeasurementSame as rms voltage
Voltage dropout (interruption)Measurement typeSame as voltage dip
LAN interfaceConnectorRJ-45
Speed and type10/100 Base-T, auto MDIX
Communications protocolTCP/IP over Ethernet
Wireless controller interfaceConnectionwireless (2.4 GHz radio)
Speedup to 700 kbit/second
Communications protocolBluetooth SPP
Power Measurements
Power, battery lifeMeasurement typeTrue RMS calculated continuously: every cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards
FrequencyMeasurement range42.5 to 69 Hz
Measurement sourceSame as PLL synchronization source
Measurement accuracy±10 mHz (10 to 110% of range, with sine wave)
Power factorMeasurement range0.000 to 1.000
Measurement accuracy±1 digit from the calculation of each measured value (±3 digits for total)
Displacement power factorMeasurement methodCalculated from the phase difference between voltage fundamental and current fundamental
Measurement range- 1.000 (leading) to + 1.000 (lagging)
Measurement accuracy±0.5% reading ±2% full scale ±1 digit
Voltage unbalance and phase sequenceMeasurement methodPositive sequence voltage divided by negative sequence voltage, per IEC 61000-4-30
Harmonic voltage and currentAnalysis windowrectangular
Analysis order1st to 50th order
Measurement accuracyVoltage / Current: 1st to 20th orders: ±0.5% reading ±0.2% full scale, 21st to 50th orders: ±1% reading ±0.3% full scale (current sensor accuracy must be included for current and power)
Measurement methodIEC 61000-4-7
Inter-harmonic voltage and current (intermediate harmonics)Analysis windowrectangular
Analysis orders1.5 to 49.5th order
Measurement methodIEC 61000-4-7
FlickerMeasurement methodIEC 61000-4-15
Plt for 2 hours and Pst for 10 minutes
Measuring range0,1 to 5 (25) depending on voltage level, modulation and frequency
Environmental Specifications
EnvironmentalOperating environmentIndoors or in covered area outdoors, up to 2,000 m altitude
Storage temperature and humidity-20°C to 50°C, 80% RH max, non-condensing
Operating temperature and humidity0°C to 40°C, 80% RH max, non-condensing
Maximum rated working voltageVoltage terminals1100 V rms
Voltage durability5550 V rms AC for 1 minute, between voltage input terminals, voltage input terminals and current probes, and voltage input terminals and case (50/60 Hz, 1 mA sense current)
Enclosure protectionIP30 (per EN 60529)
StandardsEMCEN 61326-1:1997+A1:1998 Class A
EN 61000-3-2:1995+A1:1998+A2:1998
EN 61000-3-3:1995
 SafetyEN 61010-1 2 nd Edition; 2 000
Voltage input unit: Contamination Level 2 , Overvoltage Category 1000 V CAT III, 600 V CAT IV (anticipated overvoltage: 8000 V)

Models: Fluke 1750 Three-Phase Power Quality Logger

Fluke 1750
Fluke 1750 Three-Phase Power Quality Recorder
Part#: 4756213
UPC#: 0 95969 81522 2

Includes:

  • 1750 acquisition unit
  • 1750 handheld tablet
  • 4 x 400A current probes (3140)
  • 5 Test leads and clips
  • 2GB SD Memory card (larger cards not compatible)
  • Fluke Power View and Fluke Power Analyze software
  • Power cord with international plug set
  • Ethernet cable
  • Color localization set
  • Printed Getting Started manual
  • Product CD with software and user manual PDF
  • CS 1750/1760 Rugged transit softcase

Does the Fluke 1750 measure DC voltages and Currents?

Asked by: malcolm
No, the Fluke-1750 cannot do DC currents.
Answered by: FlukeCorporation
Date published: 2024-03-28

Aside from the 2gb max, what are the other requirements for SD cards? I tried a 2gb SD card (LTSD200102GBA High Speed); it did not work

Asked by: DeMass
  • y_2024, m_11, d_18, h_5CST
  • bvseo_bulk, prod_bvqa, vn_bulk_3.0.42
  • cp_1, bvpage1
  • co_hasquestionsanswers, tq_2
  • loc_en_US, sid_1627906637876, prod, sort_[SortEntry(order=LAST_APPROVED_ANSWER_SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_fluke
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getContent, 23.35ms
  • QUESTIONS, PRODUCT
Rated 4 out of 5 by from Gets the job done! This recorder was good for an analyzer right away. Glad the PDA has a larger screen now, so it doesn't require a stylus to use the software. The SD file saving method is magnitudes slower than Ethernet. The PDA (tablet) did not come with a case or a screen protector even though the recorder is heavy duty, so I purchased an OtterBox for it. It didn't come with cable ties, so purchased some Velcro ties. The included 400A clamps were not big enough for my application, so I had to purchase larger flex clamps. All in all, it gets the job done, and with a few extra thoughts, it could be a full complete package.
Date published: 2016-12-08
Rated 5 out of 5 by from Intuitive software, very powerful, top of the line troubleshooting tool We have used various disturbance analyzers over the years, from BMI thermal paper units, to the original RPM recorders. This unit has surpassed them all in terms of ease of use and quality of information. This unit stays in the field as a work horse.
Date published: 2012-06-07
  • y_2024, m_11, d_18, h_5
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.42
  • cp_1, bvpage1
  • co_hasreviews, tv_0, tr_2
  • loc_en_US, sid_1627906637876, prod, sort_[SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_fluke
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getReviews, 23.67ms
  • REVIEWS, PRODUCT
Please enable cookies to view product reviews.
Chat with ourFluke assistant
Clear Chat