Why Ground, Why Test?

Why it is important to test your grounding system

Poor grounding contributes to unnecessary downtime, but a lack of good grounding is dangerous and increases the risk of equipment failure.

Without an effective grounding system, you could be exposed to the risk of electric shock, not to mention instrumentation errors, harmonic distortion issues, power factor problems and a host of possible intermittent dilemmas. If fault currents have no path to the ground through a properly designed and maintained grounding system, they will find unintended paths that could include people. These organizations provide recommendations and/or develop standards for grounding to ensure safety.

OSHA (Occupational Safety Health Administration) »
NFPA (National Fire Protection Association) »
ANSI/ISA (American National Standards Institute and Instrument Society of America) »
TIA (Telecommunications Industry Association) »
IEC (International Electrotechnical Commission) »
CENELEC (European Committee for Electrotechnical Standardization) »
IEEE (Institute of Electrical and Electronics Engineers) »

Good grounding is more than a safety measure—it also prevents damage to industrial plants and equipment. A good grounding system will improve the reliability of equipment and reduce the likelihood of damage due to lightning or fault currents. Billions of dollars are lost each year in the workplace due to electrical fires. This does not account for related litigation costs and loss of personal and corporate productivity.

Why test ground systems?

Over time, corrosive soils with high moisture content, high salt content, and high temperatures can degrade ground rods and their connections. Despite low earth ground resistance values when initially installed, these values can increase if the ground rods are eaten away.

Grounding testers, like the Fluke 1623-2 GEO Earth Ground Resistance Meter and the Fluke 1625-2 GEO Earth Ground Tester, are indispensable troubleshooting tools to help you maintain uptime. With frustrating, intermittent electrical problems, the problem could be related to poor grounding or poor power quality.

All grounds and ground connections must be checked at least annually as a part of your normal proactive maintenance plan. During these scheduled checks, a 20 % increase in resistance should be investigated. Once identified, the problem should be corrected by replacing or adding ground rods to the ground system.

What is a ground and what does it do?

The NEC, National Electrical Code, Article 100 defines a ground as: "connected (connecting) to ground or to a conductive body that extends the ground connection." When talking about grounding, it is two different subjects.

  1. Earth grounding: the intentional connection from a circuit conductor, usually the neutral, to a ground electrode placed in the earth.
  2. Equipment grounding: ensures that operating equipment within a structure is properly grounded.

These two grounding systems are required to be kept separate except for a connection between the two systems. This prevents differences in voltage potential from a possible flashover from lightning strikes. The purpose of a ground besides the protection of people, plants and equipment is to provide a safe path for the dissipation of fault currents, lightning strikes, static discharges, EMI and RFI signals and interference.

What is a good ground resistance value?

There is a good deal of confusion as to what constitutes a good ground and what the ground resistance value needs to be. Ideally a ground should be of zero ohms resistance.

There is not one standard ground resistance threshold that is recognized by all agencies. However, the NFPA and IEEE have recommended a ground resistance value of 5.0 ohms or less.

According to the NEC, make sure that system impedance to ground is less than 25 ohms specified in NEC 250.56. In facilities with sensitive equipment it should be 5.0 ohms or less.

The telecommunications industry has often used 5.0 ohms or less as their value for grounding and bonding. The goal in ground resistance is to achieve the lowest ground resistance value possible that makes sense economically and physically.

Speak with a specialist

Related articles

 

You might also be interested in

Chat with ourFluke assistant
Clear Chat