Fluke 1621 GEO Earth Ground Tester

  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getAggregateRating, 139.35ms
  • REVIEWS, PRODUCT
  • bvseo-msg: HTTP status code of 404 was returned;
  • Fluke 1621 GEO Earth Ground Tester
  • Fluke 1621 GEO Earth Ground Tester
Discontinued

Key features

  • Easily capture values with single-button operation
  • 3-pole Fall-of-Potential earth testing for basic measurements
  • 2-pole resistance measurements for added versatility
  • Ensure accurate measurements with automatic ‘noise’ voltage detection
  • Hazardous voltage warning offers increased user protection
  • Clearly read and record data with a large, backlit display
  • Rugged holster and design for tough work environments
  • Portable size allows for easy transportation
  • Instantly be alerted to measurements outside of your set limit, when you use the adjustable limit setting
  • 600 V Cat II
This product is discontinued or reclassified

Product overview: Fluke 1621 GEO Earth Ground Tester

The Fluke 1621 is an easy-to-use earth ground tester. For ground resistance testing, the 1621 is the first line of defense in detecting reliable ground connections. The unit features basic ground testing methods including 3-pole Fall-of-Potential as well as 2-pole ground resistance tests. Its convenient size, rugged holster, and large, clear LCD display make it an ideal field earth ground tester, for most electrical grounding work environments. With a simple user interface and intuitive functionality, the Fluke 1621 is a handy grounding tool for electrical contractors, utility test engineers, and earth ground specialists.

Specifications: Fluke 1621 GEO Earth Ground Tester

General Specifications
Measuring functions3-pole earth ground resistance, 2-pole ac resistance of a conductor, Interference voltage
Intrinsic errorRefers to the reference temperature range and is guaranteed for one year
Measuring rate2 measurements/second
Battery1One 9 volt alkaline (LR61)
Battery conditionLO-BAT is displayed if voltage drops below 6.5 V
VoltagesBetween jacks H/C2 and E/C1250 Veff maximum (effective voltage)
Between jacks S/P2 and E/C1250 Veff maximum
Climatic classVDE/VDI 3540 RZ (conforming to KWG as per DIN 40040, 4/87)
Temperature performance2Working-10°C to +50°C (+14°F to +122°F)
Operating0°C to +35°C (+32°F to +95°F)
Storage-20°C to +60°C (+68°F to +140°F)
Reference+23°C ±2°C (+73°F ±4°F)
Temperature coefficient±0.1% of range per degree Kelvin
SafetyIEC/EN 61010-1, 600 V CAT II, pollution degree 2
Dimensions113 x 54 x 216 mm (4.5 x 2.1 x 8.5 in), including holster
Weight850 g (1.9 lb), including standard accessories, volume approximately 600 cm3
Electrical Specifications
Maximum deviationsE1 Influence factorPosition
E1 Deviation influence0%
E2 Influence factorSupply voltage
E2 Deviation influence0%
E3 Influence factorTemperature E3
E3 Deviation influence2.3%
E4 Influence factorSerial interference voltage (20 V)
E4 Deviation influence0.6%
E5 Influence factorProbe- and auxiliary probe resistance
E5 Deviation influence10%
Test voltage3.7 kV
Protection typeIP 40; IEC/EN 60529
Electromagnetic compatibilityEmissionIEC/EN 61326 Class B
ImmunityIEC/EN 61326 Annex C
RE Resistance measurementMeasuring methodCurrent-voltage measurement with improved cross-talk attenuation, no compensation of measuring lead resistance, with probe (3-pole) or without probe (2-pole), as per IEC/EN 61557–5
Open circuit voltage23 to 24 V AC
Short circuit current> 50 mA AC
Measuring frequency128 Hz
Maximum permissible overload250 Veff
Measuring time8 seconds (average from when START is pressed)
Limit inputTester retains set value even if instrument is turned off (assuming battery power supply is sufficient)
Automatic changeover of resolutionRH< 7 kΩ
Resolution0.01 Ω
RH< 50 kΩ
Resolution0.1 Ω
RH> 50 kΩ
Resolution1 Ω
Interference voltage display DC + ACVmax30 Veff
Common mode rejection> 80 dB at 50 Hz and 60 Hz
Ri680 kΩ
Measuring uncertainty< 10% for pure AC and DC signals
Measuring Range
0.15 Ω to 20 ΩResolution0.01 Ω
Display range0 to 19.99 Ω
200 ΩResolution0.1 Ω
Display range20 to 199.9 Ω
2 kΩResolution1 Ω
Display range200 to 1999 Ω
Intrinsic Uncertainty±(6% of measured value + 5D)
Operating uncertainty IEC 615573±(18% of measured value + 5D)
1. If the tester is not going to be used, or is being stored for a long period, remove the battery and store separately from the tester to avoid damage from battery leakage.
2. The four temperature ranges for the tester exists to satisfy European Standards requirements; the instrument can be used over the full working temperature range by using the temperature coefficient to calculate accuracy at the ambient temperature of use.
3. Covers all deviations caused by influence quantities E1–E5. If the deviation E4 caused by high probe or auxiliary probe resistance is higher than specified flashes. Measured values are outside of the specified operating uncertainty.

Models: Fluke 1621 GEO Earth Ground Tester

Fluke 1621
Fluke 1621 GEO Earth Ground Tester

Includes:

  • Users manual
  • Two measuring leads with alligator clips, 2 m (6 ft)
  • One battery, 9 V alkaline (LR61)
  • One protective holster, yellow
  • One CD-ROM
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getContent, 98.61ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: HTTP status code of 404 was returned;
  • bvseo_sdk, p_sdk, 3.2.1
  • CLOUD, getReviews, 99.01ms
  • REVIEWS, PRODUCT
  • bvseo-msg: HTTP status code of 404 was returned;
Please enable cookies to view product reviews.