Fluke 368 FC Leakage Current Clamp Meter
Compare products: clamp meters
- Fluke 393 FC Solar Clamp Meter CAT III 1500 V
- Fluke 377 FC Non-Contact Voltage True-rms AC/DC Clamp Meter with iFlex
- Fluke 378 FC Non-Contact Voltage True-rms AC/DC Clamp Meter with iFlex
- Fluke 376 FC True-RMS Clamp Meter with iFlex
- Fluke 325 True RMS Clamp Meter
- Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex®
- Fluke 902 FC True-RMS HVAC Clamp Meter
- Fluke 369 FC Leakage Current Clamp Meter
- Fluke a3001 FC Wireless iFlex® AC Current Module
- Fluke a3000 FC Wireless AC Current Clamp Module
- Fluke 323 True RMS Clamp Meter
- Fluke 324 True-RMS Clamp Meter with Temperature & Capacitance
- Fluke 373 True-RMS AC Clamp Meter
- Fluke 365 Detachable Jaw True RMS AC/DC Clamp Meter
- Fluke 375 FC True-RMS AC/DC Clamp Meter
- Fluke 374 FC True-RMS AC/DC Clamp Meter
- Fluke 773 Milliamp Process Clamp Meter
- Fluke 355 True RMS 2000 A Clamp Meter
- Fluke 353 True RMS 2000 A Clamp Meter
- Fluke a3002 FC Wireless AC/DC Current Module
- Fluke 772 Milliamp Process Clamp Loop Meter
- Fluke a3003 FC Wireless 2000 A DC Current Clamp Meter
- Fluke a3004 FC Wireless 4-20 mA DC Clamp Meter
- Fluke 771 Milliamp Process Clamp Meter
- Fluke T5-1000 Voltage, Continuity and Current Tester
- Fluke T5-600 Electrical Tester
Key features
- True-rms measurements for accuracy when measuring complex, non-sinusoidal waveforms
- 40 mm jaw opening
- Highest resolution of 1 μA, measure up to 60 A
- Selectable filter function removes unwanted noise
- Max/Min/Average readings and hold function
- Forward-facing LED worklight for use in dark wiring cabinets
- Backlit display; auto backlight off and auto power off for extended battery life
- CAT III 600V safety rating
- Internal Memory Logging: up to 65,000 measurement points
Product overview: Fluke 368 FC Leakage Current Clamp Meter
Reduce downtime – Find leakage currents without taking equipment offline.
The Fluke 368 FC true-rms leakage current clamp meter helps users detect, document, record and compare leakage current readings over time as a means of preventing unplanned downtime, and identifying intermittent GFCI and RCD trips, all without taking equipment off line.
The Fluke 368 FC has a large 40 mm diameter jaw for work with large conductors. The clamp’s jaw is fully shielded to accurately capture very small leakage signals, and to minimize external electromagnetic interference.
The 368 FC also offers wireless data connectivity via Fluke Connect. As part of Fluke Connect — the industry’s largest system of software and more than 40 wireless test tools — the 368 FC allows you to track changes in leakage current over time, helping to identify potential problems before they turn into major failures.
What's in the box:
- 368 FC Leakage Clamp Meter
- Soft case
- 2 AA Batteries (Installed)
- Quick Reference Guide
Specifications: Fluke 368 FC Leakage Current Clamp Meter
Electrical Specifications | ||
Measurement function | Alternating current | |
AC ampere range | 3 mA, 30 mA, 300 mA, 3 A, 30 A, 60 A | |
mA / A: manual selection 3 mA / 30 mA / 300 mA: automatic selection 3 A / 30 A / 60 A: automatic selection | ||
Range / Resolution | 3 mA¹ / 0.001 mA | |
30 mA / 0.01 mA | ||
300 mA / 0.1 mA | ||
3 A / 0.001 A | ||
30 A / 0.01 A | ||
60 A / 0.1 A | ||
Accuracy – filter activated (40 to 70 Hz), filter off (40 to 1 kHz)² | 3 mA – 30 A 60 A | 1% + 5 digits 2% + 5 digits |
Frequency | 40 Hz to 1 kHz | |
Crest Factor | 3 | |
After calibration accuracy is valid for one year. Accuracy is expressed as ± (% of reading + digits). Reference conditions 23 ±5 °C and a maximum relative humidity of 80%. ¹The minimum value is 10 μA rms. ²Outside of the TC / °C 18 °C to 28 °C, 0.02 + 1 | ||
Physical | ||
Display (LCD) | Digital readout: 3300 count | |
Display refresh rate | 4 times / sec | |
Maximum conductor diameter | 40 mm | |
Dimensions | 234 x 101 x 46 mm | |
Weight | 500 g | |
Battery | 2 AA, IEC LR6, NEDA 15A, alkaline | |
Battery life | Expected battery life, without using backlight and spotlight, is more than 150 hours | |
Automatic shut-down | Meter automatically shuts down after 15 minutes of inactivity | |
Safety and Environmental Specifications | ||
General safety | IEC 61010-1: Pollution Degree 2 | |
Measurement safety | IEC 61010-2-032: CAT III 600 V / CAT IV 300 V | |
Operating temperature | -10 °C to +50 °C | |
Storage temperature | -40 °C to +60 °C | |
Operating humidity | Non-condensing (<10 °C) | |
90% relative humidity (10 °C to 30 °C) | ||
75% relative humidity (30 °C to 40 °C) | ||
45% relative humidity (40 °C to 50 °C) | ||
Protection class | IEC 60529: IP30 (jaw closed) | |
Operating altitude | 2000 m | |
Storage altitude | 12000 m | |
Current sensor action category | IEC 61557-13: Class 2, ≤30 A / m | |
Electromagnetic compatibility (EMC) | ||
International | ||
IEC 61326-1 | Industrial Electromagnetic Environment | |
CISPR 11 | Group 1 Class B | |
Group 1 | Generated inside the equipment and / or use radio frequency energy associated with conducting the energy for the device's own internal functions is essential. | |
Class B | Equipment for home appliances and residential buildings directly connected to a low voltage power supply network equipment. When this device is connected to a test object, it may exceed the emission levels produced by CISPR 11 requirements. Korea (KCC): A type of equipment (radio and communication equipment industry) | |
Class A | This product meets the requirements of industrial electromagnetic equipment, vendors or users should be aware of this. This device is intended for use in a commercial environment, instead of the home environment. USA (FCC): 47 CFR 15 B Subpart. In accordance with section 15.103 provides that the products are considered tax-free device. |
Models: Fluke 368 FC Leakage Current Clamp Meter
Includes:
- Leakage Clamp Meter
- Soft case
- Safety manual
- Batteries: 2 AA